FEATURES
Agent Release Control Panel designed specifically for suppression
release operation with:
� Four initiating device circuits (IDCs)
� Two notification appliance circuits (NACs)
� Two release appliance circuits (RACs)
� Two special purpose monitor inputs (SPMs) for manual release
request and manual abort request
� Three auxiliary relays with selectable functions
� Easily selected activity timing options
Agent release operation includes:
� Automatic extinguishing release
� Deluge and preaction sprinkler system release
� Dual or single hazard area protection
� Combined agent release and preaction operation*
� IDCs are selectable for cross-zoning or for activation from a single
detection input
� Short circuit RAC supervision
Operator interface provides:
� Status LEDs per circuit for Alarm, Trouble, and Supervisory (where
appropriate)
� Acknowledge, alarm silence, and system reset
� Operating mode and timer selection when in programming mode
Audible Escalation of Events:
� Single Audible Appliance Tone: Stage 1 activates Temporal or 20 bpm
March Time pattern; Stage 2 activates 120 bpm March Time pattern to
indicate release timer active; Release activates On Steady to indicate
release timer expired and actuator is activated
� Dual Audible Appliance Control* (Single Hazard): RAC 2 provides
a third NAC for dedicated Stage 1 Bell control; NACs 1 & 2 indicate
release as On Steady
Compatible with Listed/Approved 24 VDC coil automatic water
control valves
Required system components:
� Coil supervision module (Part No. 430687), one per solenoid control
RAC
� Maintenance Switch (Part No. 433936 or 433937), one per solenoid
control RAC
Recommended accessory (where appropriate):
� Abort Switch:
– Part No. 433940, Flush Mount
* Requires software revision 4.01 or higher
INTRODUCTION
Dedicated for Agent Release: AUTOPULSE Z-10 Sup pres sion
Release Panels provide conventional fire alarm control circuits and are
equipped with the features required for a wide variety of single or dual
hazard suppression release applications. Capabilities include automatic
extinguishing agent release, and deluge and preaction sprinkler control.
Flexible I/O Capabilities: Four IDCs allow for either four separately
monitored zones or two cross-zoned connections. Two SPMs allow
dedicated manual inputs for release or abort. Two releasing appliance
circuits (RACs) supervise to the actuator coils and activate the actua-
tors when required. The two NACs and the three panel auxiliary relays
provide status condition information.
Easy Program Selections: The operator panel has a program mode
that allows selection of panel operation type and detailed operating
selections using an easily selected sequential programming operation.
History Log: The last 50 events are stored in non-volatile memory. This
information is accessed by connecting a technician’s computer to the
service port which is also used to set the date and time.
PANEL FEATURE DESCRIPTION
Operator Panel: The operator panel has alarm and trouble status
indicating LEDs for each input and output, visible through the locking
cabinet door. Unlocking the door provides access to the Acknowledge,
Alarm Silence, and System Reset push-button switches.
Four Class B IDCs provide coverage for either two cross-zoned areas
or four separately zoned areas. IDCs are capable of supporting up
to 30 current-limited smoke detectors or electronic heat detectors as
well as manual stations and other compatible contact closure initiating
devices. IDCs are capable of Class A operation with an optional adapter
module and can be programmed as Class C (short or open initiates a
trouble) for use with current limited devices only. Single hazard agent
release applications monitor low pressure switches on IDC3 and tamper
switches with IDC4.
Z-10 AGENT RELEASE
CONTROL PANEL
Data/Specifications
AC Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarm
Trouble
Alarm
Trouble
Alarm
Trouble
Alarm
Trouble
Alarm Silenced
Supervisory
System Trouble
Relay Disconnect
Earth Fault
Agent Released
Abort Active
Manual Release
Manual Release
Zone 5 Trouble
Zone 6 Trouble
NAC 1 Trouble
NAC 2 Trouble
RAC 1 Trouble
RAC 2 Trouble
CAUTION
DISCONNECT
BATTERY AND
A. C. POWER
BEFORE
SERVICING
COIL SUPERVISION MODULE (2 AMP) 2081-9046
INSTALLATION INSTRUCTIONS 574-437 REV
MAINTAIN 1/4" SEPARATION
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER
LIMITED (YEL/BLK) WIRING
RED
NAC+
NAC-
BLK
DATE CODE: 519-958
YEL
BLK
S
PUSH AND HOLD
FIRE SUPPRESSION
SYSTEM ABORT
NORMAL
DISC.
/
DISABLE
FIRE SUPPRESSION
DISCONNECT / DISABLE
0
1
AUTOPULSE Z-10 Agent Release Control Panel
One-Line System Reference Drawing
006554
MAINTENANCE
SWITCH
ACTUATOR
CIRCUIT
IDCs 2, 3 and 4
CYLINDER
VALVE
AGENT DISCHARGE PATH
NAC 1
NAC 2
SPM 1
SPM 2
IDC 1
AGENT
SOURCE
COIL
SUPERVISORY
MODULE
RAC 2RAC 1